Master Specification
FRP Handrail and Guardrail Systems
Master specification; adapt project notes before insertion.
Project notes: Post size ______ mm · Rail size ______ mm · Post spacing ______ mm · Resin ______ · Color ______ · Mounting ______ (concrete/steel) · Toe board ______ · Infill ______ · Code ______.
PART 1 — GENERAL
1.1 Related Sections
Division 01 provisions apply. Related: Section 05 52 13 (FRP grating), Section 14 22 00 (FRP ladders), Division 26 (where dielectric isolation is specified).
1.2 Summary
Specifies FRP guardrail and handrail systems — posts, top and mid rails, fittings, infill panels and baseplates — for platforms, stairs and edges in corrosive, marine or electrical environments.
1.3 System Description
Provide handrail/guardrail to comply with OSHA 29 CFR 1910.28 and applicable building code: top rail height 1015–1120 mm (42 in) above walking surface; midrail; toe board where required; system resists a 890 N (200 lbf) top-rail load and a 730 N/m (50 plf) distributed load without exceeding code deflection. Use FRP where corrosion, weight or non-conductivity is required.
1.4 Submittals
Submit product data, post/rail section sizes, baseplate anchorage detail, load certification, COA and samples for color/fitting approval.
PART 2 — PRODUCTS (MATERIALS)
2.1 Posts & Rails
Pultruded FRP rectangular or round tube: posts typically 50 × 50 mm or 60 × 60 mm; top/mid rails typically 40 × 40 mm or round Ø 40–50 mm. Glass content ~70%; resin: isophthalic for general, vinyl ester for corrosive, phenolic for fire/low-smoke duty.
2.2 Fittings
Molded FRP elbows, tees, couplers and baseplates, mechanically fastened or bonded with compatible resin/adhesive. Stainless A4/316 fasteners and anchor bolts; FRP non-metallic fasteners where electrical isolation is required.
2.3 Infill & Toe Boards
Where infill is required, use FRP grating panel or FRP plate; toe board 100–150 mm high (FRP plate or angle) where objects could roll off.
PART 3 — EXECUTION (INSTALLATION)
3.1 Examination
Verify substrate and anchorage; confirm post spacing per design (typically 1500–2400 mm). Do not install on unsound concrete or steelwork.
3.2 Installation
Set posts plumb and anchored to baseplates; bolt or bond fittings per manufacturer detail; set top rail at code height; level rails between posts. Allow for thermal movement at long runs; use slotted connections. Do not overtighten FRP fittings.
3.3 Field Modification
Cut tubes with carbide saw; deburr and seal cut ends; re-seat and re-check fittings after cutting; do not notch rails.
PART 4 — QUALITY
Manufacture under ISO 9001:2015. Verify: post/rail sections match submittal; Barcol ≥ 35; fittings fully seated and fastened; posts plumb within 3 mm/m; top rail height within code; system load-tested or certified to 890 N point / 730 N/m distributed. Reject cracked tubes, loose fittings and missing fasteners. Inspect after thermal cycling (re-check torque).
Standards & Sources
- Industry pultruded grating metric design manual (manufacturer PDF) — pultruded tube and fitting data. Manufacturer technical data available upon request.
- ZeAllgrate — Guidelines for the Engineer/Designer (ACMA) — guardrail and access practice.
- OSHA 29 CFR 1910.28 (guardrails), 1910.23 (walking-working surfaces); ISO 14122-3 (guardrails); ASTM E84 where fire-rated.
Supplementary Design Considerations
Handrail systems are dimensioned to the guarding code that applies at the location — OSHA 29 CFR 1910 (top rail 42 in / 1070 mm, mid rail at half-height, 200 lbf top-rail load, 50 lbf/ft intermediate load) or IBC/ISO 14122-3 equivalents. Post spacing follows the load chart for the rail section; base plates are SS316 with anchor bolts matched to the substrate. The system is non-conductive, corrosion-proof and non-sparking — specify SS316 hardware for chloride service and confirm the tested load report for the exact component combination and spacing on the project drawing.
Handrail systems are dimensioned to the guarding code that applies at the location — OSHA 29 CFR 1910 (top rail 42 in / 1070 mm, mid rail at half-height, 200 lbf top-rail load, 50 lbf/ft intermediate load) or IBC/ISO 14122-3 equivalents. Post spacing follows the load chart for the rail section; base plates are SS316 with anchor bolts matched to the substrate. The system is non-conductive, corrosion-proof and non-sparking — specify SS316 hardware for chloride service and confirm the tested load report for the exact component combination and spacing on the project drawing.Get This Spec in Word
Send post spacing and mounting — ZeAllgrate returns the completed 05 51 00 handrail section with fitting schedule.